Table 6. Matrix of mortar moisture loss tests.
Unit
Mortar
Air
Test
Unit
temperature
Unit
Mortar
temperature
temperature
(C)
(F)
(C)
(F)
(C)
(F)
type†
no.*
moisture
type
1
Brick
20
68
Dry
MC-M
20
68
20
68
3
Brick
20
68
Dry
MC-N
20
68
20
68
4
Brick
20
68
Dry
PCL-M
20
68
20
68
6
Brick
20
68
Dry
PCL-N
20
68
20
68
7
Brick
20
68
Dry
MC-M
5
41
5
41
8
Brick
20
68
Dry
MC-M
20
68
5
41
9
Brick
20
68
Dry
MC-M
30
86
5
41
10
Brick
5
41
Dry
MC-M
5
41
5
41
11
Brick
5
41
Dry
MC-M
20
68
5
41
12
Brick
5
41
Dry
MC-M
30
86
5
41
13
Brick
20
68
Normal
MC-M
5
41
5
41
14
Brick
20
68
Normal
MC-M
20
68
5
41
15
Brick
20
68
Normal
MC-M
30
86
5
41
16
Brick
5
41
Normal
MC-M
5
41
5
41
17
Brick
5
41
Normal
MC-M
20
68
5
41
18
Brick
5
41
Normal
MC-M
30
86
5
41
19
Brick
20
68
Wet
MC-M
5
41
5
41
20
Brick
20
68
Wet
MC-M
20
68
5
41
21
Brick
20
68
Wet
MC-M
30
86
5
41
22
Brick
5
41
Wet
MC-M
5
41
5
41
23
Brick
5
41
Wet
MC-M
20
68
5
41
24
Brick
5
41
Wet
MC-M
30
86
5
41
28
CMU A
20
68
Dry
MC-M
20
68
20
68
29
CMU B
20
68
Dry
MC-M
20
68
20
68
30
CMU C
20
68
Dry
MC-M
20
68
20
68
* Several of the initially planned tests were not performed (2, 5, 25, 26, 27).
† Unit properties are listed in Table 4.
The tests plotted in Figure 6 were all cured in
placed back into the bags and returned to the cool-
sealed bags in the cooling chamber, as were all
ing chamber.
tests conducted at 5C (41F) air temperatures. It is
Appendix A summarizes the results of the mor-
reasonable to assume that throughout the test the
tar moisture loss tests. Figures 6 through 10
mortar was losing moisture not only to the units in
present the significant findings from the tests.
which it was in direct contact, but also to the air
Effect of unit moisture. The effect of masonry unit
within the bag. The wetter the unit, the quicker the
moisture content on mortar moisture loss was
buildup of relative humidity within the bag,
which reduced subsequent moisture loss from the
tar and unit temperature. In all six cases, mortar in
contact with the dry units exhibited a much
plastic bags during the tests supports this conten-
greater rate of moisture loss than with either the
tion. The effect of bagging the prisms can be seen
normal or the wet units. In addition, in all six cas-
in Figure 7. Due to handling, the bag surrounding
es, as expected, the wet units resulted in the lowest
one prism developed a hole that permitted mois-
rate of mortar moisture loss. While the moisture
ture within the bag to escape. The effect of the
loss of the mortar in contact with normal units was
vented bag resulted in a significant reduction in
always greater than that in contact with wet units
mortar moisture content in comparison with the
and lower than that in contact with dry units, the
mortar in the other prism. At the conclusion of the
relationships between them were not always con-
24-hr test, both prisms were removed from their
sistent. In two of the six cases, the mortar moisture
bags and returned to the cooling chamber. The rate
loss was approximately equal to the average of
of moisture loss from the mortar in the unvented
that with the dry and wet units, as exemplified in
prism then increased significantly, but the rate of
Figure 6a. In the other four cases, there was essen-
moisture loss from the mortar in the vented prism
tially no difference in mortar moisture loss be-
was virtually unaffected. Within several hours, the
tween the normal and the wet units, as shown in
moisture contents of both prisms stabilized at an
Figure 6b.
8